  1. TwBryant

    Commercial Addition at what SF is a sprinkler system required?

    Okay, I found it... IBC, 303.1, Group A, A-2, Bars. IBC 903.2.1.2 Group A-2 [F] fire sprinklers are required if... The fire area exceeds 5,000 SF, The fire area has an occupant load of 100 or more, The fire area is located on a floor other that the level of exit discharge. and IBC Table...
  2. TwBryant

    Commercial Addition at what SF is a sprinkler system required?

    An older Bar wants to add an addition to the bar that also will be used as a bar. The existing Bar is about 1,200 SF. How many square feet can be added to this bar before a fire sprinkler system is required?