Thanks for your answers,
The reason I thought 250gpm is enough was because of Table 11.2.3.1.1 in NFPA 13-2002, which states the total combined inside and outside hose (gpm) for a ordinary hazard is 250.
So, installing sprinkler system usually reduces the total required flow?
What if the...
hi,
The conditions are as follows:
-I just want to supply water for class I & III hose cabinets, there is not a sprinkler system.
-I calculate the required pressure by myself, only tell me the nominal flow capacity of the pump (gpm) and I guess a fire pump can supply up to 140% of its nominal...