  1. en2e

    Booster Pump from Ground Storage

    Thanks for the help everyone. It turned out to be an issue with main diameter and cross-connections. With some line upsizing and valving, pump seems to be working fine. @bimr and @jonr12, thanks for the tips, I'll keep them in mind as we progress.
  2. en2e

    Booster Pump from Ground Storage

    To clarify, I was thinking the pump TDH would equal target HGL, minus ground elevation at the highest point in the low pressure zone, minus static contribution.
  3. en2e

    Simple WaterCAD Question

    Which, by the way, will work for any element type.
  4. en2e

    Booster Pump from Ground Storage

    I'm working with a small town who is under consent order from the state DEQ for low system pressures. They have a 72' tall ground storage tank, and must keep it at a minimum level of 63' to have even serviceable pressures in the vicinity - when hydrants are opened for fire protection or...
  5. en2e

    Simple WaterCAD Question

    You can just select the reservoir tool and click on the junction you want to replace. WaterCAD will prompt you to confirm if you want to morph the junction to a reservoir, so just hit "Yes".