  1. ahhie

    SF6 purity requirement in 66kV switchgear

    Thank you. I measured the SF6 purity in our switchgear compartment (15 years old) using RH SF6 Analyzer 973, some are as low as 95%. Does this means we need to replace the gas? What is the minimum SF6 purity requirement for 66kV GIS switchgear?
  2. ahhie

    SF6 purity requirement in 66kV switchgear

    hi, I am working on 66kV switchgear maintenance. I like to know what is the minimum requirement for the SF6 purity (% volume). I cannot find it on the manual, it only give dew point requirement like -5 degree C for switchgear and -10 degree C for circuit breaker. Thank you.
  3. ahhie

    MK 30 Automatic Voltage Regulator

    It is our main 11kV distribution substation which feed other remote secondary 11kV substations that are in interconnected ring network configuration.
  4. ahhie

    MK 30 Automatic Voltage Regulator

    We have 3 66/11 kV system transformers (18.8/27MVA) connected in parallel. Each transformer 11kV side have tap changer to keep the voltage at 11kV. I am wondering why some of automatic voltage regulator (MK 30) failed (indicated on it display screen), hence no automatic voltage regulation if the...
  5. ahhie

    transformer fault current calculations

    Hi, I/z is equal to current for this case because the Z is in percentage. Transformer rated current divided by Z (percentage impedance) is the available fault current of the transformer at the HV voltage if the Z impedance reference voltage is HV.
  6. ahhie

    CDG Guru Needed.

    Thank you Ralph. Actually, I need the trip curve to do protection coordination. I will try Alstom again. Do you happen to know Square D MCCB? I do not know what trip curve to use for Square D MCCB type SMAF 31000. I can only find the trip curve for the MA type and cannot find SMA type in the...
  7. ahhie

    CDG Guru Needed.

    Hi, I have this relay at site which may be more than 15 years old. The relay type is CDG31EG2012JD5. This relay is 3 poles Standard Inverse curve from the number 31 but is it 1.3s/10x curve, 3s/10x curve or other? Thank you.
  8. ahhie

    Trip curve for Mitsubishi Electric NF800-S breaker and Merlin Gerin Se

    Hi, Anyone have trip curve for Mitsubishi Electric No-Fuse Breaker NFE 800-s and Merlin Gerin Selpact In=1600A with protection type DN2 characteristic? I have try on the internet but cannot find. I suppose it is very old type. Thank you.
  9. ahhie

    Moeller NZM12-1000 (ZM12) MCCB

    Hi, I have NZM12-1000 MCCB at site which I do not know much about. How to know the setting for overload time Tr is ON or OFF? This is a thermomagnetics type. Thank you.
  10. ahhie

    time/current characteristics

    ScottyUK, Thank you very much. You are great. Regards, Ahhie
  11. ahhie

    time/current characteristics

    Dear all, Where can I find the time/current characteristics for the 800A type J fuse used in Merlin Gerin LV SAIF feeder pillar (Type 1601). I have try the fuse manufacturer site - Lawson Fuses but did not find one. Hope someone can help me on this? Thank you.
  12. ahhie

    Voltage across VT secondary fuse holder

    Hi, A new 3 phase 110V VT circuit with earthed neutral, the cables and instruments connected to it have been meggered and found to be earth-free. Why 48V is measured when voltmeter is applied across the top and bottom of each of the three fuse holders? The three core cable is about 250m long. Is...