Hello,
I'm trying to model a dedicated OA system with chilled beams in Trace 700. In Trace, this translates to a main cooling coil (the AHU or dedicated outside air system) and the auxiliary coil (the chilled beams). My problem is that I can't figure out how to set up the primary air conditions...
Oh I see. As far as using energy modeling to make better design decisions, it's a privelage I don't see here very often. From what I've observed at many companies in the NY/NJ area, energy modeling is usually used to fulfil some sort of project requirement such as LEED, and it comes so far into...
Yea that's true. I did read something that mentioned that some projects needed some sort of testing of the facility 1 year after building "open-up" to validate the energy model. I think the term was called calibrating.
Drazen: You guessed right in that I have no choice but to take some packed rooftop with a fixed ton/cfm capacity. I'll try re-doing the calculations to get a better fit. The peak loads and block loads are pretty close; a difference of about 10-15% max. But that's a good way of validating zones...
I'm not sure how to simplify what I'm saying [upsidedown]
I have the required OA calcs from an Excel sheet. I inputted those values in Trace and I'm getting the cirrect OA outputs. Now, I took the block capcacity, the SA CFM, and got selections for an AHU. The CFM/ton based on the Trace file...
Well the question I have now isn't necessarily a Trace question. It's what the standard procedure for matching your load CFM from your load calculations and your CFM from your selected AHU.
I do have the SA temperatures locked, and I'd like to keep them that way so I don't have to critically look at every zone in this building every time I adjust the Trace file. I do have another problem I'm trying to figure out, however.
For the outside air calculations, we design based on the...
By design airflow I mean the SA CFM, not the OA. I contact Trane support as HerrKaLeun suggested and they were able to help me out (not at once, but they got back to me). To who's interested, the answer is below.
To specifiy the desired design SA CFM, the block cooling airflow must not be...
Hello,
I'm a beginner in Trane Trace 700, and I'm having a problem I can't figure out. I'm doing load calculations for a building. I ran the calcs and everything came out OK. The procedure for me now is to go through the OA calculations using ASHARE 62.1 excel sheet (the company advises us not...