A composite slab design for a hospital in California has been reinforced for diaphragm forces using #4 at 16 e/w. The UL design quoted (D916) called for 6x6/10x10 mesh. The design replaced the mesh with the rebar. The fire marshal says this design does not meet the UL requirement because the...