  1. rvega

    Series reactors to limit short circuit current

    Thanks everybody for your help. The series reactors have been installed with success. Finally Trech Group was the best option.
  2. rvega

    Series reactors to limit short circuit current

    Yes, I am looking for series reactors suppliers for the interconection of a cogeneration plant with the public electric grid. The paper mill was working always isolated. I'm trying with Trench Group, but I'd like to see other option. If you know another supplier could be great!
  3. rvega

    Series reactors to limit short circuit current

    I'm trying to get 3 series reactors to limit short circuit current. The nominal current is 2000 A and 1 ohm of inductive reactance to reduce the short circuit current from 34 kA to 22 kA. The dc resistence has to be as low as possible to reduce losses.