    11 kw 2pole motor burnt out connected in star

    Just a note to help any confusion. The two motors were each driven by its own inverterdrive. The motors were delivered pre wired and set up by a major manufacturer and commissioned by them. Unfortunately the commissioning engineer failed to notice the motors had been wired in star.After 1 year...
  2. speeddial

    11 kw 2pole motor burnt out connected in star

    Hi I have had 2 11 kw 2 pole pumps burn out at the same time. Both had a converter starters and were found to be connected in star.I have wired the replacements in delta and run no problem. The motors were 400 v delta 660-690 star. The manufacturer is insisting that the connection in star would...