You can test VT by two methods:
A. HV test:
1. Short all the primary terminals together including nuetral (remove the neutral from the ground).
2.Short all the secondary terminals and ground.
3. As per IEC, for 24kV rated equipment, power frequency withstand voltage is 50kV.
4. Apply 75% of 50kV...
What protections you have applied for capacitor banks?
Generally following are used for capacitor bank protections.
1. Bank overcurrent protection
a) Using bank fuses or
b) Using O/C relays
2. Over-voltage protection
3. Unbalance protection
Capacitor bank protection equipment must guard against...
What protections you have applied for capacitor banks?
Generally following are used for capacitor bank protections.
1. Bank overcurrent protection
a) Using bank fuses or
b) Using O/C relays
2. Over-voltage protection
3. Unbalance protection
Capacitor bank protection equipment must guard against...
There are three velosity settings in buchholz relay. The normal velosity setting is 1 m/s. The most senitive setting is 0.75 m/s and least sensitive setting is 1.5 m/s. Your setting is OK. If the buchholz didn't reset then you have to release the air through the small valve from where you...
The book was printed by General Electric Company in 1956 in USA.Liberary of Congress Catalog Card Number is 56-8694.
Please check at www.geindustrial.com/pm/notes/artsci/
Regards,