To clarify, what I am particularly interested in is how to select the appropriate calibration range for the lower range transmitter.
I expect to calibrate the higher range transmitter to go from zero to the flowmeter full scale differential pressure. The lower range transmitter will then be...
Thank you everyone for your input so far. There have been several questions that I'd like to answer now to help clarify the application.
The characteristics of the 4 main pumps are as follows:
P1 - Turb - 388 GPM
P2 - VFD - 194 GPM
P3 - VFD - 194 GPM
P4 - Turb - 300 GPM
All the pumps are...
I have an application where I have 4 variable speed pumps that can supply feedwater to a common header that in turn feeds up to 4 industrial boilers. It takes up to 3 of these pumps operating in parallel to handle the load of all 4 boilers. There is also a smaller, constant speed pump used for...