I am trying to remove the heat from the hydarulic fluid after it leaves the pump... in fact, after it is done doing whatever work I am asking of it (sometimes none), before returning to tank.
MintJulep - I agree/understand that I have to remove less heat from the fluid when doing work , as...
Thanks for your replies. As for the requested clarifications, I am using a heat exchanger but it is not air cooled. The exchanger is part of the hydraulic system I have, but requires chilled water input, and thus why I have the chiller... to cool this water.
As for the electric motor and pump...
I am trying to use a chiller to cool a hydraulic system, and am trying to verify if I have enough cooling capacity in my chiller. The stated maximum cooling capacity is 10.5KW.
My system starts with a 50HP motor (~37KW), and my first question is how much of that in worst case scenario can...
Thanks for all of your replies. Apologies for not properly searching previous posts/threads - this is my first time using the site and I was not familiar with search techniques or posting guidelines... many google (standard) searches before posting came up empty.
Thanks again - especially...