Sorry, I was away a few days.
Loads are mainly motors driven by VSD.
I'm not really concerned by the value itself, as it remains under 3%.
My concern was to try to calculate the value on the 13.2kV side. But it seems clear we can't.
Thanks
Thanks
Yes, transformers are loaded (40% for 1st one, 50% for 2nd one) and supply different gears, so as you said, nothing in commom except primary voltage. Unfortunately, no meters on the 13.2kV side....
My guess is less than 1%, but I was wondering if any calculation method (even...
Hi,
I have 2 transformers on which I could measure THDv on the LV side. 1% on 1st transformer (2.5MVA), 2.1% on the second one (2MVA).
Both Transformers are supplied by the same 13.2kV switchgear
Is there an easy way to calculate the equivalent THDv on the 13.2kV side?
Thanks