LionelHutz; there was about 10-15A on the generator. If I'm using a generator and a transformer, why would the power factor not matter that much?
Waross; thank you for pointing out they are not paralleled, my terminology was inaccurate- you can tell I'm new to this. Only one is loaded. I don't...
Thanks xnuke. If the only loads connected to the transformer were florescent lights and some motors, would a 0.73 power factor be considered reasonable?
I have two 75KVA transformers connected to a 3 phase 480V bus energized from a generator. The transformers are intended to back up each other to supply a sub panel in a delta to Y configuration to provide 208/120VAC 3 phase. The breakers of the load side of the transformers are interlocked so...