Thanks.
Yeah, I'm sure that the utility won't accommodate me. But, everytime they change a transformer "from Stock" I guess the consumer has to change their service panel/main breaker to be compliant. if they don't match the RMS. Still sounds hokey to me. LOL
Asking nicely and repeatedly...
Again, THANKS!
Waross you have given me a much better understanding. Yes, I agree that it is the contractor's responsibility to be sure of the serviceability and conformance but, mid-stream is a little late for an EXPENSIVE change order that could/should have been done at the onset. Wayne440's...
Thanks for the responses. The transformer is supplied by the utility company and the center has 6 separate business all served by the same transformer. The RMS is still not clear to me in that there is, I'm sure, a complicated calculation that the utility would have done when installing the...
I have an unusual (for me unusual) situation. Have been asked by electrical contractor to obtain fault current ratings for a transformer serving a shopping center that we are doing a tenant build-out for and have obtained this. The contractor is telling me that the main breaker for the service...