Remote facility with four 4160V 2600kW generators in parallel. All gen's each have a NGR on the neutral. There is voltage imbalance of 6%, regardless of which or how many generators are running, with zero load. The bus line-to-line voltage is equal (4.15kV) but the line-to-neutral varies (2.3kV...