  1. biminijoe

    Motor starting

    Thanks to all for some good leads .... I am going to double check generator mechanical operation, and AVR and woodward control on govenors. The motor does start... its just that distribution system voltage drops more then desirable. The then the generator takes about 15 seconds to stabilize...
  2. biminijoe

    Motor starting

    Thanks for all responses so far .... There can be as much as 40 to 80 KW on the line when the motor is started. Yes it is the voltage dip take is the problem I could spend some more money on the generators and upgrade the voltage regulators, add a permanent magnet field excitation and set up...
  3. biminijoe

    Motor starting

    Trying to overcome motor starting problem on axial piston pump hyd system. 50 hp Squ. Cage Motor 480 VAC NEMA CODE F Generator is 188 KVA stand-by - 169 KVA continuous Power distriubution system experiences unacceptable voltage drop when motor is started. Is it possible to reduce the...