  1. Addy71

    Experience with LIRA for cable assessment

    Does anyone have experience with using LIRA (Line Impedance Resonance Analysis) for cable testing & has compared the results with TDR, VLF tan delta & partial discharge? We are doing the latter & client wants a comparison. To my understanding, LIRA can detect physical damage to the cable but...
  2. Addy71

    motor/gen HV testing. DC or AC HV?

    We use a DC Hipot tester (Phenix) as well as a power frequency tan delta tester (Tettex + Eltel) & a PD analyzer (PD Tech + HVPD). We have wondered about purchasing a VLF source to avoid the resonators; but I am unsure if the tan delta values plus PD values & patterns at power frequency would be...
  3. Addy71

    Interpratation of the online Partial Discharge Measurement Result

    I think the more important questions are: 1. What is the coupler rating - 80 pF, 500 pF, 1 nF, 2 nF or 8 nF? - The higher the coupler rating; the larger the measured signal will be. 2. What is the frequency band in which the measurement is taken? - A lower "low cut-off" frequency will give you...
  4. Addy71

    high P.I. (with good one-minute I.R.)

    I have added it as a PDF now, should work.http://files.engineering.com/getfile.aspx?folder=dea3bb2b-ac7b-4fb5-b56c-7760bb6142c8&file=P43_October-10_R8_IR_&_PI_Draft_Standard.pdf
  5. Addy71

    high P.I. (with good one-minute I.R.)

    IEEE 43 Draft Standardhttp://files.engineering.com/getfile.aspx?folder=920e3df2-de41-4324-93e0-9a255c3f0aac&file=P43_October-10_R8_IR_&_PI_Draft_Standard.docx
  6. Addy71

    high P.I. (with good one-minute I.R.)

    I would agree with EPete that extremely high P. I. values do indicate insulation degradation. I have attached data of two identical 9.2 MW, 13.8 kV motors that I tested some months ago. These have been examined and visual indications of degradation & PD observed. A spare motor is being planned...
  7. Addy71

    high P.I. (with good one-minute I.R.)

    Here’s an explanation of Dielectric Discharge Ratio from Metrel’s “Guide to Modern Insulation Testing”: The dielectric discharge test is very useful for testing a multi-layer insulation. This test can identify excess discharge currents that occur when one layer of a multi-layer insulation is...
  8. Addy71

    high P.I. (with good one-minute I.R.)

    Here another case; this one does worry me. These are identical 30 MW, 11 kV, 2-pole gas turbine generators; commissioned in 1995. The P. I. values for two phases increased drastically for GTG 1. We've opened the generator; cleaned it (solvents + dry ice), dried it & varnished it. The P. I...
  9. Addy71

    high P.I. (with good one-minute I.R.)

    The motors are all of 6.6 kV. I do not know for sure that stress grading coatings are present; but this is quite standard for 6.6 kV motors (certainly for the first two; which are of BHEL make). The top row is for October 2012, bottom row for October 2011. Why the query about stress grading...
  10. Addy71

    high P.I. (with good one-minute I.R.)

    ElectricPete, I have seen this kind of behaviour & have seen the correlation in the capacitance & tan delta tip-ups (see the attached document). The top reading for each motor is of 2012 & the bottom reading is for 2011. Couple of these are planned for rewinds. These motors are 6.6 kV with VPI...
  11. Addy71

    Non-magnetic Retaining Rings removal from 2 pole generator rotor

    There is no way that the rotor retaining rings don't have locks, just need to find them. Some have external nuts; other have circlips. Some have both. Often; the circlip won't release till you cross 200 C. I've always used gas torches, work just fine. Induction heating equipment is a lot more...
  12. Addy71

    TVA/Corona Probe Suppliers

    PD locations based on PD Tech guidelineshttp://files.engineering.com/getfile.aspx?folder=1ad79eaa-9f45-428a-a090-da168abb6897&file=Partial_Discharge_Locations.pdf
  13. Addy71

    TVA/Corona Probe Suppliers

    PD Interpretation based on PD Tech guidelineshttp://files.engineering.com/getfile.aspx?folder=0d4e69dd-0766-4457-ae54-bbbb3229306a&file=Partial_Discharge_Interpretation.pdf
  14. Addy71

    TVA/Corona Probe Suppliers

    Hi EPete, Thanks for the slides. So, I understand that you do TVA probe checks only if the Iris system shows high values. Is that correct? I have attached a presentation explaining the cause of +ve & -ve pulses, by Cutler-Hammer. It is most logical. I get confused at times as PD Tech uses...
  15. Addy71

    TVA/Corona Probe Suppliers

    EPete, Thanks for the feedback. A few questions please: 1. I have been recommending swapping the line & neutral leads to many clients in India but no one takes it seriously. Is this a standard practice in USA? 2. For these particular 13.2 kV motors; do you have a phase-resolved PD pattern...
  16. Addy71

    TVA/Corona Probe Suppliers

    EPete, I assume the voltage rating must be based on the insulation level provided in the probe rather the arc scenario; as arc would be nominal when generator is energized from a HV test kit. Iris never had its own probe; they got it when they took over Adwel. I am looking at the Doble Lemke...
  17. Addy71

    TVA/Corona Probe Suppliers

    I am looking for a supplier for TVA/Corona Probe, other than Iris. The Iris instrument cannot be used beyond 6.9 kV. I need to localize the PD on the individual generator bars. Any feedback would be most appreciated. Regards, Aditya
  18. Addy71

    winding insullation resistance

    The 0.1 megohms is on the LV side, so machine can run. The winding IR has weakened, but the winding is not grounded. Oil filtration & dry-out can improve the IR value as required. Regards, Aditya
  19. Addy71

    Faults in a 110 MW Generator

    Glendale, Many thanks again for the input. Last couple of questions - how long did the whole process take & what was the voltage applied - one volt, some volts or higher? Will not bother you further after this one. Regards, Aditya
  20. Addy71

    Faults in a 110 MW Generator

    Glendale, Thanks for the input, this is great. Did you wrap the cable around the shaft or rotor bore or both? How long did you pass the current before reversing the polarity? Did you use a gauss meter to assess the magnetism level? Regards, Aditya