sorry I mis read your post about monitoring L2 and L2. I do take the measured KWH and divide it by 2 to get the actual use.
This brings up another question. Since half of the 8 circuits are just off L1 ,(110 volt circuits) that just happen to be on the same leg, for that appartment. My .5...
Thanks guys, I have wired several of these CT Watthour meters. But, in the past I've always just had one pair of wires to monitor. Sounds like this one will involve putting a few more wires through each CT, No big problem. I greatly appreciate everyone’s advice
That would make my life much easier. With my limited electrical knowledege I couldn't determine if passing all the L1 wires and L2 wires respectly through a CT would give me the Sum KWH or just the Average KWH of the circuits.
Thanks
I use KWH meters on my apartments to keep track of tenents electric usage. I have one unit that is not on a seperate sub-panel. Is it possible to connect a CT on each of the 8 circuits used for the one tenent space and wire all these Current Tranformers in series for each phase? This should give...