    10 lead Generator winding identification, & low voltage readings.

    I missed that too, Agreed leg to "neutral" = 277. Thanks from one Bill, to another Bill.
  2. NJ_Bill

    10 lead Generator winding identification, & low voltage readings.

    So, 1-4 + 7-10 = 480, 4-1 + 7-10 + 0 volts? If so, with winding 1-4 backwards so it was actually 4-1,what would be the voltage be between 4 to 2, 2 to 3, 3 to 4?
  3. NJ_Bill

    10 lead Generator winding identification, & low voltage readings.

    thread238-314092 I have a 10 lead generator that I have installed in series Y to supply 480 3 ph. Most of the leads where marked (unknown if correctly marked). When I run the gen set, I get 480ish volts (haven't tweaked the regulator yet) on A - B, 360ish volts B - C, and 360ish C - A. Therefor...