  1. jmsalinas1

    Non-Conductive Fence for 138kV Substation

    All I appreciate the replies. stevenal - a new fence inside would be an excellent idea the only limiting factor is space. It is already a 3 Unit substation in an area that is roughly 200'x 200'. Moving the fence in about three feet is an expensive option but if we were to want to add an...
  2. jmsalinas1

    Non-Conductive Fence for 138kV Substation

    Thanks for the suggestions. Typically the type of set up we have now is outer loop 3' outside of fence permiter with 18"-24" of crushed rock like you have mentioned. The situation here is that the substation is located in the middle of the city with a bus stop about 2 feet from the fence line...
  3. jmsalinas1

    Non-Conductive Fence for 138kV Substation

    Has anyone ever used a non-conductive fence for a 138kV Substation or similar application? I ran accross AMICO but would like other options of possible. If anyone has ever used them can you please provide some feedback? Currently I have conducted a ground study with CDEGS and in order to...