    Ventilating a Gel cell Battery Room

    1 CFM per square foot is definitely the answer, not the 10 ACH. One other item to note though. If you do the calculations to confirm the 1% by volume, you will get even much smaller numbers than the 1 cfm/sf. In general (depends on battery H2 release rates) you will get a number so low, the...