I have a pressure vessel that has a U-1 form (as well as the nameplate) that has two different sets of MAWPs and MDMTs.
One MAWP is 250 psi @ -20F to 300F and the other MAWP is 85 psi @ -20F to -50F.
This vessel is operated on a 24/7 basis between -30F and -40F.
The vessel contains anhydrous...
I have a pressure vessel that has a U-1 form (as well as the nameplate) that has two different MAWPs and MDMTs.
One MAWP is 250 psi @ 300F to -20F and the other MAWP is 85 psi @ -20 to -50F.
We operate this vessel between -30F and -40F.
The vessel contains anhydrous ammonia and is operated at...
I have a pressure vessel that has a U-1 form (as well as the nameplate) that has two different MAWPs and MDMTs.
One MAWP is 250 psi @ 300F and the other MAWP is 85 psi @ -50F. We operate this vessel between -30F and -40F. The vessel contains anhydrous ammonia and is operated at around 9"hg...