  1. zorgglub

    generator overload

    Good evening , please let me tell you a story about two gensets of 3 generators each: the first one is powered by 4045HF150 John Deere engines , with Stamford UC224D alternators. rated to 110 KVA standby.we can call it George. the second one , powered by John Deere 4045HF150 and fitted with...
  2. zorgglub

    update on ATS switches in // in Haiti

    thread238-389899 Good evening Gentlemen, a quick update on the previous post , the hospital is now fitted with a brand new 1600 Amp ATS switch , very nice but heavy as a dead donkey :). transitions from city power are now much more safe. many thanks for the advices . Best regards Jean Michel
  3. zorgglub

    Update on retaping distribution transformers

    thread238-392721 a small update for the retaping problem in Haiti : we have been readjusting the output voltage of the generators to 208v , reprogrammed the 10KW UPS to the same voltage , setting the ATS values to mi 200/max 220 v , and adjusted the transformers to 208v. No more beeps ...
  4. zorgglub

    distribution transformers cxalculation

    Dear All, we have 3 padmount distribution transformers , rated for 13.200Y / 208y-120. the line voltage in Haiti is 12.470v. we keep on experiencing low secondary voltage , and the installer of the transformer tell us that it is because of grid power , not transformer. my guess is that the...
  5. zorgglub

    LV , high current cables connectors

    Dear all, investigating electricals circuits in 3 Haitians hospitals , i keep finding odd and stranges things. the lastest is a connection between padmount transformer and ATS switch cabinet. three phases , 220 v , 300 KW circuits are connected with the system show below : i am not an expert...
  6. zorgglub

    ats switches in //

    hello Gentlemen, a company is suggesting to use 2x400a ats switches in // instead of a 800a... as far as i remember , this is not a good idea , either in terms of repartition of current , and in term of switching timing. do you have any idea about that ? any help welcome. ps : this is for the...
  7. zorgglub

    arcing on 13.7kv transformer inlet

    hi guys, it has been reported to me that on a distribution transformer (750KVA , 13.7 Kv) an arcing had caused the definitive damage of the transformer. i was wondering if some of you already experienced this kind of problem , and if the caps on the unsused HV inlets are sufficent in term of...