I have a six-way S&C Vista switch model 615. In this switch five of the ways have OCP, and one of them is not. Typically, how would the feeder connect? Would enter through a relayed connection or the non-relayed connection. I believe it can be either way, but Is there a typical or an advantage...
If I had rectangular strips of copper that were not industry standard size so no ampacity table existed for them. How would I calculate Ampacity? It seems that trying to match a specific circular mill area in the standard wire is not accurate.
I guess another way to ask is what is the ampacity...
I want 240 L-N
Can i Ground X4 tie x2 and x3 togather and use X1
wire to the device would be x4=N and x1=L
240V L-N
should work but the connection diagram is not showing it
This is your life and its ending one moment at a time.
I have 2 non-utility transformers (480-415/240) that are solidly grounded in 2 different buildings.
Building A has a single aforementioned transformer
Building B has the second aforementioned transformer and an ATS and the load
I want to feed the 3phase 4 wire load with the transformer through...
any issues with this installation?
[ol 1]
I know that the disconnect would need to be labeled for different voltages.
I Disconnect, XMFR, and Load are all located on the same steal light pole.
I All fuses 600V class.
I Disconnect and XMFR are within a foot of each other. Load is on top of light...
can not find guidance in 70E or IEEE.
This issue makes VERY little difference in the calculation BUT I still want the reference
UPS
40 bats @ 12V = 480Vdc But
Float voltage is 2.25V Per Cell so the actual voltage on the bus when maintenance is being done is 2.25 x 6 x 40 = 540Vdc
I use the...
I have a generator for a project. in this example it is a 2000KW/2500KVA .8 PF and 480V so the full load amps @ 80% PF is 3007A
However, if this same generator was running at unity power factor then the most amps that I could get from it is 2406A.
The X”d for this unit is let’s say 10%
This...