Hi all,
Recently there was single line to ground fault in my plant, below is the current based on the actual record on related relays:
* TR1 and TR2 LV winding are connected to ground with low resistance NGR (1000A
* Neutral point of generators are connected to ground with high resistance...
Hello,
In my plant there is a 34.5 kV feeder that supply very far but light load (current parameters at supply feeder: V = 34 kV, I= 21 A , PF= 0.06). The feeder use C100 CT's ( multi-tap CT 100/5) and ION 7300 to measure the load.
I found out that whenever the load was disconnected, PF reading...
Recently, one of my oil filled transformer 13.8/4.16 kV, 5 MVA tripped by 87T (GE SR-745 Relay). This transformer worked in parallel with another identical 5 MVA transformer.
Relay's event record and phasors strongly indicated that there was single phase to ground fault in phase B LV side...
Hi All,
I am trying to calculate LDC setting for a voltage regulator 34.5 kV that supplying a bus in radial, this voltage regulator connected to receiving bus using a 123,000 ft length subsea cable.
The problem that I can't find the cable specification since it is an old facility. Is it...