Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations IDS on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. electrical429

    What is the difference between circuit breaker auxiliary switches S1, S2, S3, S4 etc.?

    On high voltage circuit breaker schematics there are circuit breaker auxiliary switches S1, S2, S3, S4. All can be normally open, normally closed, late break, early make. But what is the difference between them? The only explanation that I have found anywhere states the following: Auxiliary...
  2. electrical429

    Question on switchgear interlocking. Do you need to be able to operate it while doing maintenance?

    So, the main principles of interlocking are: 1. You can't operate disconnector unless associated circuit breaker is open; 2. You can't close earth switch unless associated disconnector is open; 3. You can't Close the disconnector while the associated earth switch is closed to earth; This can...
  3. electrical429

    Why is switchgear compartment de-gassing for cable termination required only for 72.5 kV upwards?

    Gas insulated equipment containing high pressure compartments, e.g. 145kV and 72.5kV gas insulated switchgear is normally provided with “plug in” cable connectors. The normal operating practice is that no work should be carried out on gas insulated High Voltage systems on one side of a gas...
  4. electrical429

    What is multiplexing in protection relaying?

    I understand what multiplexing is, i.e. transmitting several different signals via one channel. I just want some practical examples. 1. Assuming we have 96F fibre cable, which comprises 96 fibre strands. We can either connect 96 relays via this fibre cable directly. Or we can connect all of...
  5. electrical429

    Protection discrimination times (grading margin) for LV circuit breakers

    When doing protection grading studies for HV and EHV networks usual grading margins are 200-350ms depending on relay types (fast numerical vs slow electromechanical) and circuit breaker types (fast new vacuum vs slow old oil). When doing protection grading on LV networks I believe the rule of...
  6. electrical429

    How are multicore cables normally routed via outdoor high voltage equipment steel support structure?

    Are multicore cables clamped directly to steel support structure?
  7. electrical429

    How do you calculate pilot cable 50 Hz induced longitudinal voltage from a power cable?

    If pilot multicore cable is installed next to a power cable there will be induced voltage within the pilot cable. The magnitude of 50 Hz induced voltage depends on: (a) the distance between the power cable, or line, and the auxiliary cable; (b) the magnitude of the current in the power circuit...
  8. electrical429

    Can someone please explain why you need trip isolation links in protection relay panels

    I understand that you need them to isolate tripping functions, but what would be the reason why you would want to isolate certain trip functions? Looking at attached circuit breaker DC schematic example: LK10 (light blue) BUS ZONE TRIP ISOLATION - I assume you need to remove this link if you...
  9. electrical429

    Does high voltage switchboard usually arrive on site as a whole unit or as individual panels?

    If you order high voltage SF6 indoor metalclad switchboard comprising several panels does it arrive on site from the manufacturer as a whole switchboard unit or as separate panels?
  10. electrical429

    Is there a good tutorial on transformer vector group change using cable phase swap and rollover?

    I understand transformer vector groups, however I get confused when it comes to changing phase order outside the transformer to change it's vector group. For example the following statement: "For this connection the outer HV phase conductors are effectively swapped, with phase Red connected to...
  11. electrical429

    How do you determine cable cleat spacing on a cable sealing end structure?

    Three structures, each housing one single core cable.
  12. electrical429

    Dual ratio Current Transformer thermal rating

    When you have a dual ratio CT, say 1000/500/1, and the thermal rating of CT is 100%. Does this mean that on the 1000/1 ratio you will 1000 A thermal rating and on the 500/1 ratio you will have 500 A thermal rating. Or is thermal rating independent of the ratio you choose and it will be 1000 A in...
  13. electrical429

    Auxiliary Earthing Transformer rating requirements.

    As per IEEE Std C57.32 section 6.4.2 extract below Earthing Transformer continuous rating must be 3% of 10s thermal rated current. We will be installing ZNyn11 Auxiliary Earthing transformer for the purposes of limiting 132/33 kV YNd11 power transformer 33 kV side earth fault current to 1000...
  14. electrical429

    High Impedance Earthing Transformers vs Neutral Earthing Resistors?

    So in order to provide start point reference on a delta winding of a power transformer and limit earth fault current to a certain level you can either use High Impedance Earthing Zigzag Transformer or Earthing Zigzag Transformer + Neutral Earthing Resistor. Does it matter which option you...
  15. electrical429

    Why do you need dual ratio current transformers?

    I often specify dual ratio CTs based on standards, however when producing multicore wiring diagrams I always choose the ratio which is closest to required load. I never really thought about it, but why do you actually need dual ratio CTs? Even if you have ONAN/ONAF/OFAF transformer where OFAF...
  16. electrical429

    When do you require Current Transformer in/out switches?

    Can someone please explain when do you need current transformer in/out switch the one shown on the image below. I have seen these on 132 kV high impedance differential protection schemes and 33 kV busbar protection schemes. I have also seen them on 132 kV transformer backup protection scheme...
  17. electrical429

    Typical transformer X/R ratios

    Is there a source of information that outlines typical transformer X/R ratios depending on MVA and voltage rating? Also would be helpful to have the same information for underground cables.
  18. electrical429

    Dual ratio CT parameters (Knee point voltage, class, magnetizing current, resistance)

    I mostly see dual ratio CT specs where only one set of parameters is shown. And I was always wondering if you can make out parameters for the lower ratio with given information or not. i.e.: 1. Knee point voltage. Based on the following formula Vkp = K * I(fault)/CTratio * (RCT + RL + RR) lower...
  19. electrical429

    How to know if protection relay contacts can trip circuit breaker trip coil directly (no trip relay)

    Just want to make sure that I am looking at the right thing. Protection relay output contact spec says the following: Make & Break Capacity: DC: 50 W resistive DC: 62.5 W inductive (L/R = 50 ms) AC: 2500 VA resistive (cos φ = unity) AC: 2500 VA inductive (cos φ = 0.7) I assume that if circuit...

Part and Inventory Search