  1. carlossteiner

    Cross Bonding Surge Arrestor

    I would like to know if there is a methot to determinate the kV of a cross bonding surge arrestor. The standard method as used by NGTS in the UK is to select an arrester with a Ur of 1kV per 10kA RMS through fault current at the point of installation. So if the fault level is 40kA, then the...