Hello all:
We have a Autotranformer with the data from FAT:
Sn=300/300/1MVA, 400/115/10.5kV
Connection: Yyod5
Short circuit imepedance:
HV-LV u%=12.31 at 300MVA
LV-MV, u%=0.28 at 1MVA
HV-MV, u%=0.33 at 1MVA
LV-MV, u%=84.86at 300MVA
HV-MV, u%=100.08at 300MVA
For short circuit calculation at...
We have two realay protection in HV lines Distance protection and overcurrent protection. The time settings of backup overcurrent protection for earth fualt is 1 sec. During single phase short circuit the trip issue by main distance protection and ARC start in progres. The dead time ARC is 1sec...
Please can you inform based on experience settings Id and Istab of BB protection of type relay siprotec Low impedance numerical protection 7SS/
In the substation when there are different ratio of CT from the smalest 200/1A and bigest ratio 2000/1 in bus coupler there will be problem of...