  1. bitjantuek

    Superheater and Reheater Safety Valve Requirement(PG-68)

    done1980 and e43u8, Thank you for your advise and explain krub. The total relieving capacity is (Drum 1pc + +6pc + SH 2pc + PCV) = 2458.29 t/h. If i kill 1 SH valve, it will be 2458.29 – 177.5 = 2280.79t/h. It can satisfy the BMCR-2280 t/h but normally we operated with TMCR-2191 t/h. It not...
  2. bitjantuek

    Superheater and Reheater Safety Valve Requirement(PG-68)

    Dear Sir, At the present we has the problem on main steam safety valve - passing. Now we kill this valve via install gag for SH outlet to stop leaks and protect valve. Then, can someone/specials list explain me for PG-68.2 as [i]" The discharge capacity of the safety valve, or valves on an...
  3. bitjantuek

    Safety Valve Popping Test

    Problem about one safety valve was repeated the test 13th times to gets in the acceptable range. For my opinion, test result should not be accepted if the test has been repeated more that 4 times due to valve spring properties has been changed and AI recommend likes my opinion also. But I can...
  4. bitjantuek

    Safety Valve Popping Test

    I have problem about "safety valve popping test" at Power Plant because vendor they try to achieved around 13 times for 1 safety testing. and i see in code and cannot found items that show about limit for "time of popping test". Pls advice