Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations SSS148 on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. waynegu

    Heak Shrink Tubing With Low IR Reading After Heating

    THanks dpmac. Actually I have some feeling, do you know how to test the material contents?
  2. waynegu

    Heak Shrink Tubing With Low IR Reading After Heating

    Thanks a lot for your reply. However, the situation does not match your description. After the testing, I striped the joint one layer by one layer and meggered each layer as well. Then I found out there is one heat shrink stress control tubing with very low IR reading. When I did the testing...
  3. waynegu

    Heak Shrink Tubing With Low IR Reading After Heating

    Hi, I am working on a 33kV cable project and using the heat shrink joint kits for the In-Line Joints. I meggered the cable before jointing every time and the 5kV DC IR (core - sheath) reading was always around 400GOMHS/1min, and I also meggered the cable with the new In-Line joint after 3...
  4. waynegu

    VLF of MV/HV cables Frequency?

    To my experience & knowledge, VLF is too strong for cable joints, especially for aged cables. If you only want to test the PD in cable but not a HV withstand test, maybe the OWTS testing is the better option. Even for HV withstand test, I recommend AC resonant testing with PD testing. The only...

Part and Inventory Search