  1. peter53

    Electrical discharge to earth of motor bearings

    ScusaMe, thanks for your input i'll certainly follow the links that you have posted as i clearly need to understand more about vibration and motors in general. electricpete, I'm hooking up later with a trainer from UESystems to help me analyse some of my issues and will post further information...
  2. peter53

    Electrical discharge to earth of motor bearings

    ScusaMe, all the info i can get is that the motor is 3 phase, 6600volts, rpm 2990 and that it is an ex rated motor as it is located in a gas storage area.
  3. peter53

    Electrical discharge to earth of motor bearings

    Another bit of info i just found out is that the motor shaft is ceramic coated as to protect the motor NDE from this type of problem?
  4. peter53

    Electrical discharge to earth of motor bearings

    Skogsgurra, On site there 3 different locations for these 3 phase 6600v blower motors. Each location has 4 motors and named as phase 1, phase 2, phase 3 [just a location name] on 1 motor on phase 1 the NDE has the 100hz issue as does 1 motor on phase 3. Would i be correct in assuming that if...
  5. peter53

    Electrical discharge to earth of motor bearings

    I'm not sure if they are fed from the same transformer but i'll find out today and post the answer, thanks for your help i appreciate it.
  6. peter53

    Electrical discharge to earth of motor bearings

    Thats very interesting as i have found the same symptom on another motor at another location but on the same site. If this is a supply problem what would be the best way to prove this issue compared to a bearing issue.
  7. peter53

    Electrical discharge to earth of motor bearings

    Dan another company do the vibration analysis what i find using ultrasound is a buzzing sound which is backed up by a spectralyzer showing dB and hz, basically i find peaks every 100hz with a small peak every 50hz which indicates fluting. As we are 50hz supply thats where i'm looking for...
  8. peter53

    Electrical discharge to earth of motor bearings

    Thanks guys you have been very helpful
  9. peter53

    Ultrasound Inspections of Bearings

    Is there anyone who is exprienced in diagnosing problems on motor bearings using ultrasound as i have a few issues i'd like to discuss.
  10. peter53

    Electrical discharge to earth of motor bearings

    Thank you for your kind reply although i have just been told that these motors may be DOL so i assume the problem of discharge through the bearings must be comming from some other source perhaps. I assume i would now need to use a voltmeter and test the motor casing to earth.
  11. peter53

    Electrical discharge to earth of motor bearings

    I'm currently undertaking ultrasound inspections of some 6600 volt soft start motors and appear to be getting indications of fluting whereby i might be getting a discharge to earth through the motor bearings. Iknow VFD controlled motors can cause an induced voltage on the motor shaft but not...