  1. kobiyani

    EN 50522 earthing of power instalations exceeding 1 kV AC - calculation of actual touch voltage

    OK! now we are starting to get close. however, the reference from IEC set of standards into IEEE is strange. i do know the IEEE 80. however, i am straggling to figure out the IEC methodology to handle the tough voltage, and there are gaps in the system, as far as can understand. i really hope to...
  2. kobiyani

    EN 50522 earthing of power instalations exceeding 1 kV AC - calculation of actual touch voltage

    Thanks for the information. however, the figure 1 in page 80 in your mentioned file is providing the ALLOWED TOLERABLE touch voltage. I was asking about the calculation of the actual developed tough voltage which needs to be lower than the value from figure 1. moreover, this figure 1 is included...
  3. kobiyani

    EN 50522 earthing of power instalations exceeding 1 kV AC - calculation of actual touch voltage

    Hello, The European standard EN 50522 is describing with full details how to evaluate the touch voltage. Item 5.4.2 is depicting a design process which is summarized in a flow chart in Figure 5 in the standard. In my case: The criteria of earth potential rise (Ue) < double the allowed touch...