We have been asked to provide design and cost estimates for 270TR of -40F ammonia refrigeration for a series of large blast freezer cells. Requirement: Do so with lowest ammonia charge possible (less than 500 pounds in any case, to fall below CalARP inclusion threshold minimum). Four (4) 70TR...
Compositepro's observation about not going into a vacuum is a good one. This would limit the design temperature to -28F. However, ammonia will operate with reasonably good efficiency down to -40F. A good purger takes care of the air. Ammonia vapor volume increases drastically as the...
Ammonia vapor driven off in the generator or reboiler of the ammonia absorption refrigeration system contains more water vapor than one would anticipate. It is not yet refrigerant grade. Further rectification is required up the column through reflux injection or other suitable cooling means...
This is meant for "virk" who asked about a low temperature DX ammonia application on October 7th. A new DX control system accurately predicts evaporator liquid feed requirements based on refrigerant vapor quality measured within the evaporator. The technology is called Predictive Direct...