Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: urded
  • Order by date
  1. urded

    80% rated breakers

    80% rating only applies to continuous loads. Not non continuous loads. you can load a standard breaker (80% rated) up to 100% of its rating. You multiply the continuous load x 1.25% You then add the noncontinuous load at 100%. The rating of the breaker has to be more than the sum of those two...

Part and Inventory Search