Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. yinger

    How do I set file location ACAD LT2000?

    Rememberfolders was not a valid command, could it be that I am using acad LT and you are using the full version of autocad? The "start in" folder is a box on the properties window under the shortcut tab. Tom, Thanks for your continued advice on this.
  2. yinger

    How do I set file location ACAD LT2000?

    Thanks Tom, where do I find REMEMBERFOLDERS system variable? Also when I changed the start in box the program would lock up, I thought it could not find Drawing1.dwg so i put one in the start in folder but that did not help, I still got an error message. Tom
  3. yinger

    How do I set file location ACAD LT2000?

    I have not been able to figure out how to point ACAD LT 2000 to my dwg files folder. In tools, options, dwg file location is not one of the options?
  4. yinger

    Arrester selection for system with neutral grounding resistor

    Normally our 13kV wye systems are solidly grounded. But a customer has asked for a 400 amp 10 second NGR. I think I need to change from a L-N rated arrester to L-L. Is there an IEEE paper that confirms this? Is it it the IEEE Green Book? What are the drawbacks to using the higher rated arrester?
  5. yinger

    Cost Reduction by Adding HRG Units

    Fault detection equipment does not need to be added at all, it only makes fault location easier. There are many ways to assist in fault location starting with the origional ground lights and improving to the pulsing fault locators built into the high resistance grounding system. Also high...
  6. yinger

    Busbar Drilling

    If you drill a hole in the buss bar and do not use it, it reduces the cross sectional area which lowers the current capacity linearly. However, in a copper buss bar the thermal conductions is very good and the heat is dissipated upstream and downstream from the hole which greatly mitigates this...
  7. yinger

    Resistors in rotor-circuit

    The resistors that remain in the motor circuit are refered to as permanent slip resistors. The resistance is not intended to contain the maximum conveyor speed, this would have been done in the speed reducer ratio. I think this is a designed installation, not a modification to use surplus or...