  1. CBGUY

    Getting 47N trips when on generator but never on utility.

    I am not the lead guy. They are all saying that the Basler relay should not react to 8% THDV. I saw the scope, it had weird zero crossing shifts, a flat spot between positive and negative at 180 degrees. The rest was normal switching power supply,etc along the rest of the sinewave.. Years ago...
  2. CBGUY

    Getting 47N trips when on generator but never on utility.

    Device BE3-47N. tripping when set for 10%, never trips when set for 15% DRANETZ reports 1% or less. Waveform has flat spot at at zero crossing. Two devices do exact same thing. I think Specifying engineer has too tight a value. Any ideas. Load is a data center and building mechanical. Happens...
  3. CBGUY

    48VDC UVR coils holding in for too long

    Has anyone ever dealt with DC Undervoltage Release coils taking a long time to drop out. I have never had this problem with AC coils. These should be less than 100ms but are ocassionally hold as long a 900ms. I am thinking residual magnetism, any ideas?