Hi,
I am posting a few pics of chiller connection. Actually i have space constraints to accomodate valve package of chiller. I have two questions. The first one is it right to install Y strainer in a slightly tilted position coz i have less room to install it faceing downwards as you can see in...
Hi,
Yes its a normal Primary-Secondary setup. As per the theory i have referred authors are suggesting a Modulating valve in Decoupler pipe for a Variable Primary systems only ( it is understood that to keep minimal flow through chiller in low load conditions a modulating valve is installed )...
Hello,
I need help in calculating the Size of Decoupler pipe in my project. I heard the pipe size should be the size of header of the chiller which is 8" for my project. And also do i require to install any kind of control valve, if yes, what type of valve it should be, and from which point it...