The problem with the acutherm option is that like most linear diffusers, the air inlet is centered on the diffuser outlets and I would need the inlet to be on one end in this case.
It might seem like an insignificant requirement but I need to stick with it.
I'll try to run a fluid simulation...
Berkshire,
Are you saying to angle the perforated plate towards the diffuser outlet on the right hand side to within 11-10 inches of the outlet?
Also, would Solidworks fluid simulation be of any help here? I have access to it but not sure if it would be of any help.. has anyone had experience...
Thank you all for the suggestions. It has been a little while since I have been able to get back on here. I haven't had time to research the static regain method but here is my shot at the perforated plate idea. If you take a look at the attached image of a rough 2D layout, would this be what...
HVAC Engineers,
Need your advice on the design of a makeshift supply air diffuser that would provide consistent air velocity across the entire opening.
Due to the constraints of this project, I need to come up with a way to insure consistent air velocity across a diffuser that will be at a...