  1. ajlimuran

    VCB EXPLOSION

    This is the photo after explosion.http://files.engineering.com/getfile.aspx?folder=c4ca22af-b251-45fb-b5aa-0e07340fb45d&file=20140825_133818.jpg
  2. ajlimuran

    VCB EXPLOSION

    Sir, we opened checked the VI as we found out that there is current leaks between contact force spring conductor insulted coupling rod due to possible insulation failure. Please see pics...
  3. ajlimuran

    VCB EXPLOSION

    Sir, The VCB is properly handling in lifting, the main issue on this , why the VCB explode when synchronize after 3 hours?
  4. ajlimuran

    VCB EXPLOSION

    Sir it is withdrawble VCB. Please see VCB insulating rod evidence of damage.http://files.engineering.com/getfile.aspx?folder=e900dd92-87ce-4335-8624-2bf6d90afaac&file=20140825_132300.jpg
  5. ajlimuran

    VCB EXPLOSION

    What would be the root cause of 3 time explosion of the VCB?
  6. ajlimuran

    VCB EXPLOSION

    Sir the generator is connected directly to the grid.
  7. ajlimuran

    VCB EXPLOSION

    To All Experts, Specs of the VCB are below; VD4 ABB - 17.5 KV/630 Amperes/ 25 KA Our plant is diesel/bunker C power plant supply the small island. The unit is status is on going commissioning and it is synchronize to the grid. The diesel generator rated 13.8 KV and 2.1 MW capacity connected...
  8. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Dear All, I will raise this concern because , recently after we tried to back the unit online after replacing the fuse, explosion occurred again but now fuse are okay. During last explosion I observed that there was arcing evidence originated from the VCB. The relay indicates current...
  9. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    The PT is installed in the switchgear. Yes power cable is connected from generator to switchgear. What do you mean the small details ? Why the bus PT limiting fuse not blown but generator PT blown?
  10. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Im confuse also because, generator potential transformer fuse is always experience blowing fuse but the unit is synchronized to the GRID then why is my bus PT is not affected and its configuration is the same, wye connected primary and wye secondary and broken delta.
  11. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Yes Sir, there are many power plant connected in the GRID. I am looking for a solution to operate the plant in ungrounded system what to do because fuse blown twice. First move, we replace the withdrawble PT and fus, then thesame fuse blown.
  12. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Sir Zanoter we are connected directly to grid. Assuming 90% all faults is cause of ground faults due to sub-trasmission lines. In case there is a line to ground fault in the grid, since my generator is ungrounded or floating nuetral , the effect is the unfaulted phases increase twice or trice ...
  13. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    To all, What will be the best solution so that i can run the unit in ungrounded system? It is okay to change the generator PT from wye connected primary to open delta? What is the effect? Thanks all you Sir.
  14. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Sir Slavag, there is no installed damping resistor in the secondary of the broken delta which is connected to the relay input. What is the ferro-resonance ? This is cause PT fuse blown?
  15. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Sir, The generator nuetral is not grounded.
  16. ajlimuran

    UNGROUNDED SYSTEM GENERATOR 13.8 KV

    Hi, To all, We have 2.1 MW Diesel Power plant supply the small grid , generator rated voltage of 13,8KV and ungrounded or floating nuetral . Our problem is the generator potential transformer wye connected primary and wye connected secondary and broken delta connected secondary , primary PR...