Willard3 I respect your opinion but....
I may have stated the problem incorrectly lead you down the wrong path, I apologize. I want to limit the rise to 15 degrees. So, for a typical summer looking at 95F, you need about 210 CFM for every KW, therefore, revised heat loss of 220KW gives me about...
OK.......
It is an electrical room with 3 1900kw VFDs and several MCCs. I have not done this type of calculations in 25 years rusty and not trusty.
the VFDs are ~96.5 eff.=66.5kw x 3 = 199500w + other equipment; roughly total 250kw.
250,000 watts is my heat loss from the equipment = 853,035...