If i have G+4 Building and have 2 1/2'' FHC 6 nos at 4th floor, 3 at 3rd floor and 5 on each 1st and ground floor then what will be the size of individual branches to each floor and of the main riser. the system is of wet standpipe. Plz attached reference tables as well.
Wishing all professionals a nice time.
If i have G+4 Building and have 2 1/2'' FHC 6 nos at 4th floor, 3 at 3rd floor and 5 on each 1st and ground floor then what will be the size of individual branches to each floor and of the main riser. the system is of wet standpipe. Plz attached reference...
Sir,
thank you for your reply. NFPA 14 limits the pipe size to 4'' for stand pipe. I want to know how many fire hoses can be served by this 4'' pipe and when i will increase the size of the pipe.
Hi everyone,
I am new in the design of fire fighting systems can any one provide me a good reference regarding size of standpipe for different numbers of fire hose cabinets for all classes(1,2,3).