Thank you all for your answers, but I think I wasn't clear enough about the system I am working on. It is not a HVAC, but a cooling system for an alternator. None of the branches will be shutdown because if so, a component of the alternator will overheat.
And yes the RO will provide more than...
Good morning LittleInch,
I wanted to make sure I didn't make mistakes in my reasoning. Here is how I proceeded.
1- Calculate the head loss of the system with the desired flow in each branch.
2- Determine the additional pressure drop required to assure the desired flow in each branch and to match...
Hi everyone,
I am currently working on a cooling system. I need to choke the piping network with restriction orifice plates in order to assure the desired flow in each branch and to make sure that the pump will deliver what it should. The thing is, I don't know how to size those plates, I would...