Hi dbill74,
Coil icing up at such low velocity which will greatly shorten compressor life as well.
Evap Coil const Cu/Cu- 8 rows /12 fins/inch ?
Design ambient is for Middle East-Kuwait.
I will again discuss this with the manufacturer.
Thanks,
Hi,
we are using DX- Ducted split units and the data sheet I received from manufacturer shows the evap. coil face velocity 250fpm. As per our requirement cooling demand is high with less air flow- T.C.C - 68 TR - Airflow 15600 cfm
My question is;
At this fpm the air passing over the cooling...