Thanks. I had seen that, but guess I was thinking they might have used a different strength/grade steel back in 1980, so was wondering if anyone had an older manual.
Does anyone have spans table on Tenslivent Deck (era, 1980's... ).
Looking for deck capacity for a deck that is called out to be:
"1 5/16" steel deck, 22 gage, galvanized, Tensilvent 125-22 as manufactured by Wheeling Corrugating Company "
It is spanning +/- 5'-6" to 6' max.
Any help is...
Does anyone have spans table on Tenslivent Deck (era, 1980's... ).
Looking for deck capacity for a deck that is called out to be: "1 5/16" steel deck, 22 gage, galvanized, Tensilvent 125-22 as manufactured by Wheeling Corrugating Company "
It is spanning +/- 5'-6" to 6' max.
JAE - I saw a...
a little more info.
The bottom of the floor system is around 11'-0". The bottom of the lintel is about 8'-0". So I was wanting lintel to carry wind load to the jambs (which carry load up to floor diaphragm and down to slab on grade).
So basically lintel is independent of floor diaphragm...
Designing a garage lintel. Simple gable roof. Garage is 26' x 30'. Garage door lintel span = 18' and is on the gable end. There is a floor above, but floor joists are parallel to lintel, so not picking up floor load (are at least ,minimally picking up load).
If I use a steel lintel with...