dear all i have aquestion below paragraphs
NFPA 13 (2010 edition)
8.15.4.4 Large Openings. Closely spaced sprinklers and draft
stops are not required around large openings such as those
found in shopping malls, atrium buildings, and similar structures where all adjoining levels and spaces are...
dear all i would like to ask about if it acceptable or not to connect fire hose reel 1.5" from sprinklers network directly after z.c.v i have searched NFPA 14 and didn’t find what allow or prevent and thanks a lot in advance
dear all i would like to ask about if it acceptable or not to connect fire hose reel 1.5" from sprinklers network directly after z.c.v i have searched NFPA 14 and didn’t find what allow or prevent and thanks a lot in advance .
hello every one i have a question about fire hydrant as you know NFPA doesnt explain how to determine flow rate or pressure or distance separating hydrants so if any one has a guideline in this topic or information i will be thankful and thanks in advance .
trashcanman' yes i use water for cooling the the tank i cant find a source for 0.1 gpm/ft2 i know that min density is 0.15 according to nfpa but at work they use 0.1 so i wanted to make sure
if i have a tank of fuel and i want to design cooling system for it i get water flow rate from equation Q= Area*Factor
Factor is 0.1 gpm/ft.sqr and Area is Area total = shell area + roof area ? is that right ?