I apologize for the misplacement of the post, simply habit. Thank you both for the help and ill be talking with my mentor today about it. I had to use the white sheet because model space didn't show the hidden lines and i wanted to make clear of what the walls actually were, but none the less...
I am currently interning, so forgive any informality, and am trying to layout waste and vent plan for a dental clinic with sinks on a peninsula with no accessible wall for vent piping near by. I have included a screen shot of the situation and lengths, i was aware that a 2" vent pipe could go a...
DrRTU, Thank you for the detailed response.
Our set up ended up being in-floor heat along the border of the wash bay, completely separate from the detail bays, 20x20 heated pads outside the entrance and exit for snow melt. We were not allowed to go through the roof of the building, not ideal i...
Yes, they are pulled along a belt system while in neutral. But I ended up putting my original plan of two NO2 and two CO sensors controlling two exhaust fans to the outside.
Hello,
First post so bear with me on the formality. I am interning and currently working on a future detail center/automated car wash building and am running into issues with the contractor and owner about how many CO and NO2 sensors are needed and in what rooms. There are two wet detail bays...