Dear met11,
Thanks for your interest.
I apologies for the confusion over the SetP, I was sizing for a multiple tanks here, just let's say Let's just assume 9.5 barG is the one for further discussion.
With respect to your suggestion that unwetted case is not a valid scenario, my calculation...
Dear All,
I have re-attached the attachment via Link here.
To be more spcefic, the Hot oil used is Dowtherm Q Heat transfer Oil.
For Wetted Vessel Case (i.e. Hot Oil vaporization case)
I performed flash using Hysys to get the boiling point of Hot Oil 419 C at the relieving pressure i.e...
Dear All, I am looking for pointers to design for PSV for Hot Oil Drain Tank with N2 Blanketing System.
I am designing the PSV based on Fire case and Wetted vessel scenario, and I have made the following basis and would like to know if they are correct.
During External Fire Scenario, hot oil...