  1. ffllyyeerr

    Power Factor Meter for 200 KW grid tied generator

    Hi: It's a 2400 V, 3-Ph generator - 2-20:1 PT's & 3-CT's. PF/VAR controller is an older Basler (analog) SCP 250. I suspect it's doing a decent job but need it has no output so there's no way to tell. Thanks.
  2. ffllyyeerr

    Power Factor Meter for 200 KW grid tied generator

    Anyone know of a good meter to measure, adjust & monitor PF for such an application?
  3. ffllyyeerr

    Reactive Droop Compensation vs PF & AVR

    That's a good question but I suspect so as it's a rural electric co-op and their interconnect requirements are minimal to none.
  4. ffllyyeerr

    Reactive Droop Compensation vs PF & AVR

    I am working on a grid tied, 200 KVA, 2400 V synchronous generator hydro powered (Pelton Wheel) currently inop with symptoms pointing to a failed static exciter which is to be verified shortly. The generator is old without documentation. The field resistance measures 3.6 ohms through the...