thank for your answers but I think it's not enough
Initial value :
200 KVA v=400V PF=100% and I= 288.7 A
bus Operating voltage :=388V
operating load = 188 KVA (after circuit breaker)
VA=1.73 V I
I know we calculate operating voltage from voltage drop but we need also operating Amps and...
Hello
Hello
I have a load= 200 KVA PF=100% so Amps = 288.7 but in load flow analysis load=191 KVA and Amps = 280.2 before circuit breaker , and load=188 KVA and Amps=280.2 after circuit
breaker the length of cable = 10 m why this difference ?
thank you...