David hi thanks for the response. The 0.6 of figure at the source end is lagging. This figure is what I expected. Because of the mag current. Yet the loadflow model suggests it should be 0.95. which I don't understand. The issue is that meter operator is certain that their reading of 0.6 is...
Guys hi,
Looking for a quick and simply response to a technical issue regarding overall site power factor.
Situation. 3km of 132kv cable feeding a 56MVA transformer (132/11.5/11.5). 30 metres of 11kv cable connected to a 11kv switch panel. The load at the 11kv switchable is 3MVA. Local meter...